FLAME ARRESTER
Model
SFG
Series
Flame Arrester
Product Description

NOMINAL SIZE
- 1", 1-1/2", 2", 3", 4", 6", 8", 10", and 12"
- 14" through 40" sizes are available upon request.
- Available EN 12874:2001 Certified Model.


CONNECTIONS
- ANSI/ASME B16.5 Class 150 Flange
- KS/JIS 10K Flange


Protect process line or system from potential ignition source Easy installation and simple mechanism Available in size 1” to 40”

Drilling conforming to ANSI/ASME B16.5 for class 150 flanges, or KS/JIS 10K flanges In-line type model installed process line system which flammable gas or vapor flows.
Bi-directional Flame Arrester and should be installed within 20 times the pipe diameter from a potential ignition source.

▶ Consult our factory for special application.


Specifications

InstallationVertical, recommend Required drain plug for horizontal installation
TypeIn-line flame arrester
ClassificationDeflagration flame arrester, Bi-directional
Normal working pressureBelow 1.0 barg(standard speciafication)
Explosion gas groupIIA(standard), IIB/IIC(for special application)



Materials

PART NAMEMATERIALS STANDARDMATERIALS OPTIONAL
BodyCarbon Steel, 304 S.S, 316 S.S,AluminumHastelloy, Alloy 20, Monel, Inconel
Flame Element304 S.S, 316 S.SHastelloy, Alloy 20, Monel, Inconel
Element Housing304 S.S, 316 S.SHastelloy, Alloy 20, Monel, Inconel
Stud Bolt and NutC.S, 304 S.S316 S.S




Basic Ordering Information

1. Model and type
2. Fluid Handling
3. Operating Temperature & Pressure ranges
4. Size and Connection
5. Material
6. Distance from potential ignition source